About the RS485 communication anti-interference method

RS485 is a common communication method. For the problem of RS485 communication anti-interference, the following are some effective solutions:

1. Use shielded twisted pair

In practical applications, RS485 communication lines can use a shielded twisted pair, and the shielding layer is connected to the ground at a single point, which can effectively suppress the coupling of electrical fast pulse group interference to the communication line.

shielded twisted pair

2. Add a ferrite magnetic ring to absorb interference

Adding a ferrite magnetic ring at the entrance of the equipment can effectively absorb interference. At the same time, increasing the number of turns of the communication line in the ferrite magnetic ring can increase the absorption effect of interference.

ferrite magnetic ring

3. Add TVS for overvoltage protection

Add TVS tubes between the two ends of the RS485 bus to the ground. When the amplitude of the electrical fast pulse group interference voltage coupled to the RS485 bus is high, the interference voltage will be clamped by TVS to achieve the purpose of protecting the RS485 transceiver.

TVS

4. Use a V-type (hand-in-hand) bus structure

Resolutely avoid star and cross-connections. If it cannot be avoided, use repeaters or hubs. The length of the branch line from the bus to each terminal device should be as short as possible, generally not exceeding 5 meters.

5. Avoid strong electrical interference

Do not walk with strong electricity. If you cannot avoid it, it will be better to keep a distance of more than 0.5 meters.

6. Real grounding of the AC power supply for the chassis and equipment

Good grounding is required to prevent damage to the 485 equipment by accidents such as lightning strikes and surge impacts.

7. Install terminal resistors

If the distance exceeds 100m, install 120Ω terminal resistors at the beginning and end of the bus.

Install terminal resistors

8. Intermediate segment disconnection method

By disconnecting from the middle, check whether the device is overloaded, the communication distance is too long, and the impact of a certain device on the entire communication line.

9. Single wire pulling method

Simply pull a line to the device separately, which can be used to rule out whether the wiring (such as being too close to power cables, inverters, and other facilities) caused the communication failure.