CNG Desulfurization Process

CNG stations typically use a room-temperature dry desulfurization process, often employing tower-type desulfurization equipment. Dry desulfurization offers high purification efficiency, simple equipment, and convenient operation. Tower-type equipment also requires minimal floor space. However, replacement or regeneration of the desulfurizer results in certain pollutant emissions, and waste desulfurizers are difficult to recycle. Desulfurizers used in room-temperature dry desulfurization include activated iron oxide, high-efficiency iron oxide, refined desulfurizers (such as a combination of carbonyl sulfide hydrolysis catalyst and zinc oxide desulfurizer), activated carbon, and molecular desulfurizers. The latter two utilize adsorption desulfurization, which is costly. Currently, iron oxide-based desulfurizers are commonly used.

desulfurization equipment

Iron oxide primarily removes hydrogen sulfide from natural gas and can also remove some organic sulfur. The desulfurization principle is that hydrogen sulfide and iron oxide come into contact, forming iron sulfide and iron sulfide. Its main chemical reaction is:

  • Fe2O3*H2O + 3H2S = Fe2S3*H2O + 3H2O
  • Fe2O3+3H2S = Fe2S3+3H2O
  • Fe2S3*H2O + 3/2O2 = Fe2O3*H2O + 3S
  • Fe2S3 = 2FeS + S
  • FeS + S = FeS2

Hydroxy iron sulfide is highly active and can achieve precise desulfurization when operated at a temperature of 28-35°C, and the moisture content of the desulfurizer is maintained at 25%-35%. When the moisture content of the natural gas entering a CNG station is very low, the hydrous sulfide quickly loses water, rendering it inactive. The operating temperature of a CNG station also fluctuates with the ambient temperature and is difficult to maintain at around 31°C. Therefore, the desulfurization efficiency of a CNG station is far inferior to that of activated sulfide. Assuming the incoming natural gas meets Class II quality requirements as specified in GB17820, with a hydrogen sulfide content of less than 20 mg/m3, the desulfurization requirement is less than 15 mg/m3. This represents a removal rate of only 25%. However, sufficient contact time and proper water retention in the desulfurizer can still achieve the desired desulfurization results. According to information, when the natural gas contains a high hydrogen sulfide content and a water content of at least 4% (w/w), using activated iron oxide desulfurization can still achieve good results.

Using tower desulfurization equipment

Iron sulfide desulfurizers can be regenerated. The regeneration principle is that in the presence of water, iron sulfide reacts with oxygen to convert into iron oxide and free sulfur. The main regeneration reaction is:

Fe2S3*H2O+3/2O2=Fe2O3*H2O+3S.

The oxygen in natural gas can regenerate hydrous iron sulfide, but sustained regeneration is difficult at very low water contents. Under normal circumstances, CNG stations do not regenerate desulfurizers. Spent desulfurizer and sulfide are transported for centralized disposal. When regeneration is permitted, technical measures must be in place to effectively control the oxygen-containing regeneration gas, control the exothermic temperature rise during regeneration, and ensure the harmless treatment of regeneration waste gas.

High levels of light hydrocarbons in natural gas can clog the desulfurizer pores and cover the surface, rendering the desulfurizer ineffective. Desulfurizers can be centrally loaded using baskets, boxes, or directly in bulk. The loading height should be appropriate. If there is pressure loss on the desulfurizer, the desulfurizer should be loaded in layers, and each layer should be equipped with measures to prevent sulfide dust from clogging and dispersing.

Harmless treatment of regeneration waste gas

The desulfurizer dosage depends on the desulfurizer’s composition and properties, the hydrogen sulfide concentration in the natural gas, the operating pressure and temperature, and the contact time. It should be calculated based on experimentally determined reaction equilibrium constants. The design dosage can also be determined based on technical data (such as working sulfur capacity) provided by the desulfurizer manufacturer and the set desulfurizer replacement cycle. The dosage of activated iron sulfide can be simply calculated using the following formula:

  • V—volume of activated iron oxide desulfurizer, m3
  • K—operational safety factor, which can be 1.3;
  • W—hydrogen sulfide content in natural gas, mg/m3 (baseline);
  • Q—gas supply capacity of the CNG station, m3/d (baseline);
  • n—number of annual desulfurizer updates, a-1
  • f—working sulfur capacity of the new desulfurizer, % (W/W);
  • p—bulk density of the new desulfurizer, kg/m3
  • u—actual hydrogen sulfide removal efficiency of the desulfurizer, %.

The desulfurization tower diameter can be calculated using the following formula:

  • D – calculated inner diameter of the desulfurization tower
  • Q – maximum hourly flow rate of natural gas through the desulfurization tower (baseline conditions);
  • P – desulfurization tower operating pressure (absolute pressure);
  • V – linear velocity of natural gas passing through the desulfurization tower when empty. When the natural gas sulfide content is high, use the lower value required by the desulfurizer; otherwise, use the higher value.

The desulfurizer layer height can be calculated using the relationship between the desulfurizer volume V and the desulfurization tower diameter D.

Basic desulfurization tower design parameters, such as the gas velocity (expressed as tower linear velocity or empty tower replacement ratio), contact time with the desulfurizer, unit resistance of the desulfurizer layer, and the thickness of the desulfurizer layer that can be loaded, should be obtained from the desulfurizer manufacturer’s technical data.