Compressed Natural Gas (CNG) stations are high-pressure, flammable, and explosive sites. Equipment safety distances are the core line of defense against leaks, explosions, fires, and other safety incidents, directly affecting the safety of personnel, equipment, and the ambient environment. The article, based on the 《Design Code for Compressed Natural Gas Supply Stations》 (GB51102-2016) and 《Technical Standards for Automotive Refueling, CNG and Hydrogen Stations》 (GB50156-2021), Clearly stipulated the safety distance requirements for seven types of core equipment, including CNG tube trailers, compressors, and CNG storage group. It considers both intra-station equipment spacing and distances to external environments, providing a reference for CNG station construction, operation, and safety management.

1.Core Principles and General Requirements
- The safety distances of equipment in CNG stations must follow the the three major principles of leakage 、explosion and fire prevention. All inter-equipment spacing should comply with standards. Clear boundary markings must be provided between operational areas and auxiliary service areas. Open flames or spark-emitting locations are strictly prohibited within operational areas, and asphalt pavement should not be used on station roads.
- The station should be surrounded by non-combustible solid walls, with a height not less than 2.2 m relative to both the internal and external ground levels, further strengthening the safety barrier.
- The following standards cover all core requirements for spacing between equipment within the station, between equipment and external buildings or structures, and between equipment and personnel activity areas.
2. Specific Safety Distance Standards for Various Equipment
CNG Tube Trailer
As a mobile high-pressure gas storage unit, CNG tube trailers require safety distances that guarantee unloading or refueling operation safety and protection of surrounding equipment. Fixed unloading or refueling positions within the station must strictly comply with the following standards:
- Distance from open flames or sparks: ≥25 m
- Distance from production buildings such as compressor rooms or pressure regulation rooms: ≥ 6 m for storage volumes ≤ 5,000 m3; larger storage volumes require proportionally increased spacing.
- Distance from CNG dispensers or CNG unloading columns: 2–3 m, accommodating the operational length of CNG hoses.
- Distance from the edges of primary station roads: ≥ 6 m; secondary roads: ≥ 4 m
- Distance from station boundary walls: ≥ 5 m
Additionally, tube trailer parking areas must have clearly marked boundary lines, and the storage of flammable or explosive materials around the parking area is strictly prohibited.
CNG Compressor
The CNG compressor is the high-pressure power core of the station. During operation, it is Capable of generating heat and mechanical sparks, so spacing requirements are strict.
- Distance from CNG storage groups: ≥ 5 m (total storage volume ≤ 1,000 m3); for a bigger storage volumes, spacing should increase to 10–25 m.
- Distance from CNG dispensers: ≥ 6 m, to stop equipment interference in case of refueling leaks.
- Distance from spark-generating equipment such as generators: ≥ 15 m
- Distance from house areas, schools, or other densely populated sites outside the station: ≥ 40 m
- Distance from high-rise residential buildings: ≥ 30 m
If the compressor is installed outdoors, the distance to auxiliary station buildings should be ≥ 12 m, and it must be located away from high-voltage power lines to avoid electromagnetic interference.
CNG Storage Groups
CNG storage groups are the core of high-pressure gas storage. Spacing must be set according to total storage volume:
- Outdoor storage groups may be equipped with protective canopies, but safety passages must not be blocked.
- For storage wells with a total volume greater than 200,000 m3, they must be divided into multiple zones, and the distance between groups must be ≥ 20 m.
CNG dispenser
The CNG dispenser, as the terminal refueling equipment, directly contacts CNG vehicles. The spacing must consider both operational safety and personnel protection.

Generator
The generator maybe produce electrical sparks during operation and is a key fire prevention device within the station. It must be located away from high-pressure flammable and explosive areas.
- Distance to CNG daughter station (CNG storage group): ≥20m
- Distance to Compressor and Pressure Reducing Skid: ≥15m
- Distance to CNG dispenser: ≥12m
- Distance to open flame locations outside the station: ≥30m
- The generator shall be arranged in the auxiliary service area outside the operation zone.
Non-explosion-proof electrical equipment must be kept away from explosive hazard areas, and the distance to the boundary of explosive hazard areas shall be ≥3m to prevent safety incidents caused by electrical sparks
CNG vehicle (refueling status)
During refueling, the CNG vehicle is a mobile flammable and explosive carrier, and parking distances should be strictly controlled.
- Distance to other vehicles waiting for refueling: ≥4m, to avoid collisions causing leaks.
- Distance to CNG dispenser: ≥1.5m, ensuring safe connection of refueling hoses.
- Distance to CNG storage group and Compressor: ≥10m
- During refueling, vehicles shall stop the engine and apply the handbrake; the driver shall evacuate to a safe area.
- Loitering or maintenance around the vehicle is strictly prohibited.

3. Guidelines for standard implementation
Reducing distances without authorization is strictly prohibited. If site constraints require compression of spacing, it must be assessed by a professional organization, with enhanced measures such as explosion-proof and leak-prevention implemented, and distances shall not be less than 80% of the standard requirement.
For outdoor equipment layout, the outer edge of the equipment shall be the starting point; for indoor layout, openings such as doors and windows of the building shall be the starting point.
Regularly check safety distances;, promptly remove obstacles around equipment, and ensure safety passages remain unobstructed. During equipment maintenance or servicing, temporarily expand the safety warning zone, and any violation of operation rules is strictly prohibited.