Common faults of fuel dispenser oil-gas separator

The fuel dispensing device is a legal measuring instrument, and the oil-gas separator is one of its core components and is a high-failure part. Personnel responsible for maintaining fuel dispensers need to understand their performance characteristics to handle faults efficiently. Oil-gas separation device failures are usually divided into two types: gas infiltrates into the oil and cannot be separated; or the oil-gas separation device’s exhaust port discharges oil outward.

Bluesky fuel dispenser

1. Causes of Failure to Separate Oil and Gas

From the bellows node below the oil-gas separator to the bottom valve inside the oil tank, any joint, flange, or valve on the entire pipeline has poor sealing. Because the pipeline is under negative pressure, a large amount of gas will enter the pipeline. When the total imported gas exceeds the separation system’s carrying capacity, an abnormal oil-gas mixing situation occurs, which often weakens the oil pump’s self-priming efficiency and interferes with measurement accuracy. The treatment measure is to investigate the root cause, repair the leakage points of air and oil, and then return to normal operation.

2. Causes of Oil Discharge from Exhaust Pipe

The design of fuel dispensing equipment and the layout of oil-gas separation devices are based on the premise of underground oil storage tanks. If an elevated oil tank is used, it will definitely cause fuel to enter the exhaust pipe. As an emergency measure, the exhaust pipe has to be closed. The joint between the oil-gas separator end-cover air outlet and the air-outlet copper pipe must be tightly sealed with oil-resistant rubber. However, when sealing the air outlet, the gas in the pipeline must be emptied to prevent the fuel dispenser from being unable to discharge oil due to air resistance.

A too-narrow pipeline arrangement or a stuck one-way bottom valve in the oil storage tank will cause oil overflow from the oil outlet pipe, which requires careful investigation.

During fuel dispenser operation or maintenance, if the switch is operated repeatedly without discharging oil through the oil gun, it can also cause oil to discharge from the air outlet pipe. A feasible solution is to turn on the switch of the oil gun, discharge a little oil into the container, and then the oil discharge action of the air outlet pipe will stop.

Self-Priming Fuel Dispenser

3. Outlet Valve Failure

The typical failure situation is that the outlet valve is stuck. Because the lower part of the outlet valve is connected to the low-pressure chamber, impurities in the low-pressure chamber easily invade this part and cause the valve core to get stuck. If the outlet valve cannot open, the oil supply will be insufficient and abnormal noise will occur; if the outlet valve cannot close, oil and gas may not separate. The treatment plan is to clean the lower part of the outlet valve.

4. Outlet Valve Failure

The float is immersed in oil for a long time. If the float has defects such as holes or virtual solder joints, oil will infiltrate the float’s internal cavity, increasing its weight. When the external liquid level rises, the float still cannot rise. At this time, the air outlet valve cannot be closed. In addition, if the equipment operates for a long time, due to wear or other factors, the air outlet valve and the air outlet valve seat cannot fit closely, and the high-pressure chamber cannot establish the preset pressure value. When too much oil flows into the normal pressure chamber, and the parallel valve part does not return oil in time, the liquid will overflow from the air outlet pipe. At this moment, the equipment should be shut down immediately for maintenance work.

5. Parallel Valve Failure

The large float may have oil infiltration and cannot float up due to the increase in its own weight, so it cannot perform the oil return action. At this time, the oil will overflow from the air outlet pipe. If dirt accumulation in the low-pressure chamber is excessive and the parallel valve is stuck and cannot return oil, oil will also leak from the air outlet pipe.

The response method is to clean the low-pressure chamber of dirt regularly. When this fault occurs, you can remove the device or unscrew the screw plug at the lower part of the parallel valve to check whether the float, valve hole, and valve seat are operating normally. After clarifying the cause, carry out maintenance or replace damaged components.