Detailed Explanation of Gas Station Unloading Procedures

Regardless of the management system, gas stations all involve the unloading and acceptance of fuel, which involves the responsibilities of the shipper, carrier, and receiver, and how these responsibilities are handled. Controlling the unloading and acceptance process at the gas station is crucial to preventing losses. The unloading procedure is divided into three stages: before unloading, during unloading, and after unloading. These stages must be performed in sequence.

Detailed Explanation of Gas Station Unloading Procedures

1. Before Unloading

To fully release static electricity and stabilize the fuel level in the tanker truck, this stage should last at least 15 minutes.

1) Tanker Truck Entering the Station

Guide the tanker truck into the unloading area, ensuring the cab faces the exit, the engine is off, and the handbrake is engaged. If the fuel needs to be weighed, the unloading personnel should verify the delivery slip information (fuel type, tonnage, delivery unit, and vehicle license plate number) according to the supply and distribution department’s delivery plan.

  • After verification, the unloading personnel report to the gas station manager.
  • After approval, the unloading operator accompanies the vehicle to the weighing unit designated by the gas station manager for the first weighing.
  • After unloading, with the gas station manager’s approval, the unloading operator accompanies the vehicle to the designated weighing unit for a second weighing. During weighing, both the unloading operator and the driver leave the vehicle. After the weighing operation is completed, the unloading operator properly keeps the weighing slip, along with the “Gas Station Oil Product Inbound Slip”.

Tanker Truck

2) Setting up isolation

After the tanker truck has come to a complete stop, the unloading operator uses isolation cones to isolate the unloading area from the outside world. The isolation cones should be as far away from the unloading port as possible, and unauthorized personnel and vehicles are not allowed to enter.

Setting up Isolation for Tanker Truck Entry

3) Securing tires

The unloading operator should use both hands to drag the triangular blocks to the bottom of the front and rear tires of the tanker truck, securing them, respectively, to prevent accidental slippage.

4) Connecting the grounding wire

Reliably connect both ends of the grounding clamp to the designated location on the tanker truck (or the metal part closest to the tank body) and the electrostatic grounding device.

5) Verify Documents

Verify the type and quantity of oil on the tanker truck delivery slip. If incorrect, immediately contact the supply and distribution department before proceeding.

6) Prepare Protective Equipment

Prepare or wear oil-resistant gloves, non-slip shoes, safety glasses, respirators, and safety helmets.

7) Confirm Tank Capacity

Based on the level gauge report or manual measurement, confirm the oil level in the tank. Add the incoming oil quantity to the remaining oil level. If the sum exceeds the tank’s maximum safe capacity, immediately contact the supply and distribution department before proceeding.

8) Prepare Equipment

Place the unloading equipment (unloading hose, return air hose, flow meter, sampler, oil sample bottle, measuring cylinder, density meter, aluminum drum, aluminum funnel, etc.) in appropriate locations and confirm their integrity.

9) Place Fire Extinguishers

Place at least one 35kg wheeled dry powder fire extinguisher within the tank area, and at least two 8kg or 4kg portable dry powder fire extinguishers within a 2m radius of the unloading port.

10) Check Seals

For tank trucks with lead seals, check that the seals or tags are intact and that the seal or tag number matches the delivery note. If not, immediately contact the supply and distribution department before proceeding to the next step.

11) Measuring Oil Level in Tank Trucks

For tank trucks where boarding is possible, the unloading operator, wearing appropriate protective gear (oil-resistant gloves, non-slip shoes, safety glasses, respirator, safety helmet, etc.), should board the tank truck and manually measure the oil level or empty tank level. If the oil level is 5mm lower than the oil level on the delivery slip, or the difference between the empty tank level and the empty tank level on the delivery slip exceeds 5mm, or the difference in oil loss calculated from the tank capacity table exceeds 3‰, the supply and distribution department should be contacted immediately before proceeding to the next step.

12) Taking Oil Samples

For tank trucks where boarding is possible, the unloading operator uses a sampler to collect a 500ml oil sample from the bottom of the tank truck from above (closing the tank lid after collection) and pours it into a measuring cylinder. Then, using an iron bucket, a 20L oil sample is taken from the tank truck’s pipeline from the unloading port. For tank trucks where boarding is not possible, the unloading operator takes a 40L oil sample from the unloading port, and takes another sample from the unloading port after the oil in the pipeline has been drained.

13) Oil Sample Inspection

Measure the density of the oil in the graduated cylinder using a hydrometer to ensure it meets the requirements (reference data: diesel density 0.80-0.86 g/ml; gasoline specific gravity 0.70-0.76 g/ml). If the oil density is unacceptable, immediately contact the supply and distribution department before proceeding to the next step.

Observe the oil in the graduated cylinder and the iron drum for any sediment, water, abnormal odor, or abnormal color. If everything is normal, take a sample from one of the graduated cylinders as a retention sample for the gas station.

If any abnormalities are found during the inspection, immediately contact the supply and distribution department before proceeding to the next step.

Oil Sample Inspection

14) Inspection and Confirmation

The unloading personnel first inspect the above procedures, filling out the “Unloading Inspection Form” item by item and signing it. After the unloading personnel completes the inspection and signs, a third-party employee conducts a second inspection of the above procedures, filling out the “Unloading Inspection Form” item by item and signing it for confirmation.

If two or more types of oil are being unloaded from the same tanker truck into different tanks, an “Oil Unloading Inspection Form” should be completed before each unloading to confirm the procedures followed.

2. During Unloading

1) Opening the Valves

Instruct the tanker truck driver to slowly open the unloading valves to begin unloading.

2) Safety Observation

During the unloading process, the unloading personnel and driver must not leave the unloading area. Carefully observe the unloading valves, unloading pipelines, and flow meters to ensure they are leak-free and functioning normally; ensure no outsiders enter the tank area and that the surrounding area is normal. In case of an emergency, take immediate emergency measures. If thunderstorms or other abnormal weather occur, stop unloading immediately.

3) Closing the Valves

Close the unloading valves, pour the remaining oil from the unloading pipeline into the tank, and open the tank’s vent valve.

Unloading Oil from Tanker Trucks

3. After Unloading

1) Confirming the Quantity

Print the level gauge report to confirm the unloaded quantity.

2) Filling out forms

Fill out the “Gas Station Oil Receipt Form” and have it signed by both the tanker truck driver and the supplier. If there is a loss greater than 3‰, contact the supply and distribution department immediately before proceeding to the next step. (For tankers requiring weighing, perform this step after the second weighing).

3) Sealing oil samples

Fill out the “Oil Sample Seal” form and have it signed by both the supplier and the tanker truck driver. Seal the oil sample bottle stored at the gas station.

4) Tanker truck departure

The unloading operator guides the tanker truck safely away from the gas station. (If no vapor recovery device is used, after unloading, let the tanker truck stand for 5 minutes to allow the surrounding vapors to dissipate before starting the engine).

5) Storing equipment

Organize and store the unloading equipment, and lock the unloading port.

6) Storing oil samples

Arrange the oil sample bottles neatly and orderly in the oil sample box according to the oil name and arrival date, and lock the oil sample box.

Each truckload of fuel samples must be stored for at least 3 days. If a previous truckload of fuel has been sold for more than 3 days before the next truckload is added to the tank, the sample from the previous truckload must be stored until the next truckload is added.

In the sample container, after newly collected samples are stacked in the same tank, the previous sample from the same tank should be promptly poured into the tank to minimize the number of samples.

If fuel from two suppliers is stored in the same tank, the sample from the first supplier must be stored for at least 8 days. This is to allow for separate testing of the samples in case of a complaint, thus determining the supplier’s responsibility.