Does the solenoid valve affect the accuracy of the fuel dispenser?

When the fuel dispenser is preset, the large valve is not closed when the refueling volume is about to reach the preset value, which means that the flow rate has not decreased, which directly leads to an overshoot of the oil volume and the actual refueling volume exceeds the preset value, thus affecting the accuracy of the fuel dispenser. This is mainly caused by the failure of the solenoid valve to close in time or the existence of a fault. The solenoid valve plays a vital role in the fuel dispenser, which controls the flow rate and metering accuracy of the oil.

solenoid valveS

Common faults that affect the accuracy of fuel dispensers and solenoid valves:

1. The valve closing amount setting value is too small;

2. The control of the electric control valve is reversed;

3. The output problem of the electric control valve;

4. The electric valve is blocked by impurities;

5. The quality problem of the electric valve itself;

Troubleshooting steps:

1. Check the valve closing amount setting value, the default value is 0.25, if it is a large flow of 70L/min, set it to 0.50, and 45L/min is set to 0.30. ;

2. Check the direction of the electric valve and whether the signal line of the large and small valves is connected to the output end of the large and small valves on the power board. If the large and small valves are connected in reverse, closing the small valve first will not affect the refueling speed and cause no large valve;

3. Measure whether the output voltage of the large and small valves on the power board is normal;

4. Aluminum chips enter the electric valve. Disassemble the electric valve and clean it. The reason is that the joints in the pipeline were not cleaned during processing;

5. If the above measures have been taken and the large valve has not moved, the solenoid valve needs to be replaced.

 