Equipment Layout of CNG Booster Stations

1. Layout Principles

CNG booster stations should be enclosed by walls as required. The fire safety distance between the station’s process facilities and external buildings and structures should comply with relevant national regulations. Fixed parking spaces for gas cylinder trailers should be allocated based on the number of gas cylinders; overhead communication and power lines should not cross the gas station. The boiler station should be divided into zones. Generally, it can be divided into a front area, a production area, a gas filling area, and an auxiliary area. The layout of each zone should adhere to the principle of smooth flow of production processes, vehicle traffic, and pedestrian traffic, while maintaining maximum separation between them.

CNG booster stations

1.1 The connection between the front area and the outside should be smooth.

Vehicle entrances and exits should be separate to minimize impact on external traffic. The layout of roads within the station should comply with relevant national regulations and meet the passage needs of extended vehicles such as CNG transport vehicles. Fixed parking areas for CNG transport vehicles should be provided as needed. The process facility area should have vehicle collision protection facilities.

1.2 Areas with the same hazard level within the station should be grouped.

The fire separation distance between process facilities (including CNG transport vehicles) within the station should comply with relevant national regulations. If the distance between the compressor room, regulator room, distribution point room, and gas cylinder group (storage well) meets the relevant regulations, fire-resistant partitions conforming to the specifications may be used, and the fire separation distance is not limited. Gas cylinder trailers should be handled in accordance with the gas cylinder group regulations.

1.3 Land use should be economical while meeting safety requirements.

Sufficient green space should also be provided.

2. Vertical Layout

2.1 The perimeter wall of the CNG station should comply with GB50156.

The perimeter wall in the station front area should preferably be integrated with green space.

2.2The CNG station entrance and exit should be determined by the external roads.

The refueling area should also be determined based on this. The slope of the CNG vehicle entrance/exit and internal roads should not exceed 6%, and should preferably slope outwards from the station. CNG vehicle parking and refueling/filling spaces should preferably be designed with a level slope.

2.3 The entire station should be arranged at the same elevation as much as possible.

When terrain constraints necessitate a stepped layout, all zones should be positioned at the same elevation whenever possible.

 2.4 Organized Emission Requirements.

The slope of the station floor should accommodate rainwater runoff and floor cleaning.

2.5 Station Requirements.

The indoor floor level of buildings and structures within the station should preferably be 0.3m or more higher than the surrounding floor level. The floor level of open-air process facilities and gas filling islands (columns) should be 0.15~0.2m higher than the surrounding floor level.

2.6 The compressor room should preferably be arranged in a single-story layout.

The height of the vent pipe inlet in the station area should be 2m or more higher than the equipment platform and 5m or more higher than the ground level.

2.7 Requirements Before and After the Compressor.

Outdoor natural gas station pipelines before the compressor should preferably be buried underground, with a pipe top elevation of not less than 0.5m and preferably below the frost line. High-pressure pipelines after the compressor should preferably be buried underground (in trenches), but can also be arranged in low-level or high-level overhead layouts.

3. Compressor Room Layout

3.1 The fixed side of the compressor room should be adjacent to the control room.

If a reserved space is available, it should be located on the expansion side. Depending on the compressor size and other factors, the expansion side should have space or passageways for compressor maintenance and removal. If a buffer tank is present, it should be located outdoors.

3.2 Compressors should preferably be arranged in a single row.

When other equipment (such as dehydration devices) is also located in the compressor room, in addition to maintaining a distance of 2m or more from the compressor, effective vibration-damping measures must be in place.

3.3 Distances within the Compressor Room.

The clearance between passageways and compressors within the compressor room should be greater than 1.5~2.0m, and the clearance between the compressors and the walls should be greater than 1.2~1.5m. For single compressors with a displacement less than 40m³/min, a smaller clearance value can be used; for those greater than or equal to 40m³/min, a larger value should be used.

3.4 Height of the Compressor Room.

The height of the compressor room should ensure the ease of lifting and moving the equipment. The net height from the bottom of the hook to the top of the compressor (including piping) can generally be designed as 1 times the compressor height plus 1m.

3.5 Calculation of the compressor room height formula.

The “heat intensity” of the working location should not be too high. It can generally be checked and calculated using the following formula:

H≥12.3φ∑NF

  • Where: H–Net height of indoor roof (or lower chord of roof truss), m;
  • φ–Heat dissipation coefficient. 0.15 for water-cooled compressor units, 0.65 for air-cooled units;
  • ∑N–Total installed power of the compressor unit’s motor, kW;
  • F–Indoor area, m2.

Gas Storage Equipment Layout

4. Gas Storage Equipment Layout

  •  If the gas storage equipment is configured according to a multi-pressure system, it should be arranged sequentially according to high, medium, and low pressure groups. Each level can be further grouped, and the total volume of each group should not exceed 4m3.
  •  Small-capacity gas cylinders should be fixed on independent supports and preferably arranged horizontally. The width of a horizontal cylinder group is limited to the length of one gas cylinder. The gas storage equipment interface should not face personnel. A retaining wall should be installed at the interface surface whenever possible. Above-ground (including semi-above-ground) gas storage facilities should be equipped with sunshades and rain protection.
  •  There should be operational space for replacing gas cylinders, as well as a site or access for hoisting or replacing cylinder assemblies.