Gas station planning is crucial in the construction process

The division of dangerous areas is crucial in gas station planning. Therefore, the location of gas stations should be divided according to the dangerous areas of explosive gas environments. Safety principles must be strictly followed when planning gas stations.

Divided into three areas

Zone 0: Explosive gas environment. The space above the oil tank that is not filled with inert gas is Zone 0.

Zone 1: An Explosive gas environment may occur. For example, during normal operation, there may be a place where flammable substances may leak due to the need to take out products or open and close the lid, such as an area with a radius of 1.5m centered on the exhaust port of the oil tank.

Zone 2: An Explosive gas environment is unlikely to occur. For example, a place where flammable substances may leak due to corrosion, aging, etc.

Pay attention to these aspects around the oil tank

  • The space above the surface of the oil inside the tank is divided into Zone 0.
  •  The space inside the manhole (valve) well, with the spherical space with a radius of 1.5m (0.75m) centered on the vent pipe mouth and the spherical space with a radius of 0.5m centered on the closed oil unloading port, is divided into Zone 1.
  • The cylindrical space within 1.5m from the outer edge of the manhole (valve) well, 1m high from the ground, the spherical space with a radius of 3m (2m) centered on the vent pipe mouth, and the spherical space with a radius of 1.5m centered on the closed oil unloading port and extending to the ground are divided into Zone 2 (Note: The explosion hazard area of the vent pipe mouth of the gasoline tank using the oil unloading oil gas recovery system is indicated by the number in brackets).
  • When a dike is set up around the storage tank, the area from the outer wall of the storage tank to the dike, whose height is the height of the dike top, is Zone 2.
  • Oil unloading site: The space with a radius of 1.5m from the oil filling port of the oil storage tank (the oil unloading port of the tank truck) is designated as Zone 1.

Zone diagram around the oil tank

Dangerous points next to the gas pump cannot be ignored

The division of explosion hazard areas of gasoline dispensers shall comply with the following provisions:

  • The internal space of the dispenser housing is divided into Zone 1.
  • The truncated cone space with the center line of the dispenser as the center line, the ground area with a radius of 4.5m (3m) as the bottom surface and the plane with a radius of 3m (1.5m) 0.15m above the top of the dispenser as the top surface is divided into Zone 2.

Work area distribution map