The emergency shut-off valve is a device used to cut off the flow of fluid in an emergency, usually used in liquid or gas pipeline systems. They play a vital role in the event of a spill, fire, or other emergency. The following is a detailed introduction to the emergency shut-off valve:

Effect:
The main function of the emergency shut-off valve is to quickly cut off the fluid in the pipeline in an emergency to prevent leakage and reduce the risk of accidents. This is critical for safety in liquid or gas pipeline systems, especially in the chemical, oil, gas, and other industries.
Working principle:
Emergency shut-off valves usually consist of a valve body, an actuator, and a control system. When the system detects an emergency (such as leakage, fire, etc.), the control system will send a signal to the actuator, which quickly closes the valve and cuts off the flow of fluid. This reaction speed is breakneck and can prevent fluid leakage in a matter of seconds. When the pressure in the pipeline returns to normal, the valve will automatically close, and flow will resume.
Type:
According to different application scenarios, emergency shut-off valves can be divided into liquid emergency shut-off valves and gas emergency shut-off valves.
Liquid emergency shut-off valves are usually used in the petroleum and chemical industry, liquefied natural gas, and other fields, while gas emergency shut-off valves are used in natural gas, liquefied petroleum gas, and other gas pipeline systems to protect pipelines and equipment from accident damage.
Note:
When using the emergency shut-off valve, you must pay attention to safety and avoid misoperation. At the same time, components such as valves and springs require regular maintenance and replacement to ensure the valve operates normally.
Installation location:
Emergency shut-off valves are usually installed at key locations in the pipeline system, such as inlets and outlets or important branches. This minimizes the loss of leaks and ensures that the flow of fluid can be shut off immediately in the event of an emergency.
Advantages:
Emergency shut-off valves can quickly cut off pipeline flow and protect equipment and pipelines from accidental damage. At the same time, the emergency shut-off valve can also reduce leakage and pollution and protect the environment.
How to install correctly?
- The valve shear ring of the shut-off valve must be flush with the base surface of the refueling island, with an error not exceeding 13mm.
- The sand level buried in the refueling island or fuel dispenser trough must not exceed the connection position of the shut-off valve’s lower thread and the inlet pipe.
- Each valve body must be individually secured to a metal mounting bracket using a U-clamp.
- The sealant should fill the root of the pipe thread and the second and third threads of the pipe joint. Remember to use oil-resistant sealant and allow 24 hours for curing to achieve the best sealing effect. The use of PTFE tape (Teflon tape) is strictly prohibited, as it can easily cause oil leaks during subsequent use.
- Connect and tighten the shut-off valve to the oil pipeline. Do not allow the shear ring to be under stress during installation.
- Each valve should be pressure tested individually. The test pressure must not exceed 0.35 MPa.

How can we reduce the risk of accidents?
- In the event of a collision with the refueling machine, the shut-off valve will disconnect at the shear groove, automatically cutting off.
- In the event of a fire or other special circumstances, the low-temperature fusible switch of the shut-off valve melts at approximately 74°C, triggering the valve and immediately cutting off the fuel supply.
Overall, emergency shut-off valves play a vital role in the safe management of pipeline systems. Their quick response and reliable performance make them an important device for protecting personnel and equipment.