During the unloading, transfer, and refueling process, static electricity will be generated due to the friction between liquids or between liquids and equipment such as pipelines. When static charge accumulates to a certain extent, static discharge will be formed, which may cause fire and explosion accidents. The effective means to prevent static electricity is static grounding, which can effectively dissipate static charge.

1. Concept of static grounding
Static grounding is to connect storage containers, pipelines, and equipment to the earth through metal wires and grounding bodies to form an equal potential. Cross-connection refers to connecting metal equipment and pipelines with metal wires to form an equal potential.
All devices in explosion-hazardous places and fireplaces in gas stations must be electrostatically grounded. Grounding devices are strictly prohibited from being shared with grounding devices of electrical equipment.

2. What requirements should static grounding meet?
Static grounding at gas stations is a key measure for safe production, which is related to the safety of life and property of employees and surrounding personnel. The implementation process must strictly follow the relevant specifications and standards (such as GB 50156 “Technical Standards for Automobile Gasoline, Gasoline and Hydrogenation Stations” and GB 13348 “Electrostatic Safety Regulations for Liquid Petroleum Products”). The electrostatic grounding of gas stations should meet the following requirements:
1) Anti-static grounding devices should be installed at the beginning and end of the oil pipeline laid on the ground or in the trench. The grounding resistance is not greater than 30Ω.
2) Anti-static grounding devices should be installed at the automobile unloading site in the gas station for tank truck unloading. Electrostatic grounding devices installed for bridging of oil unloading facilities should be able to detect whether the bridging is good and have alarm functions.
3) Metal wires should be used for bridging of elbows, valves, flanges, and other joints of oil pipelines in explosion-hazardous areas.
4) The grounding resistance of the anti-static grounding device is not greater than 100.
5) There should be no fewer than 2 grounding bodies, which can be laid vertically with angle steel and steel pipes. The buried depth should not be less than 2.5m, and the distance between two grounding bodies should not be less than 2.5m. The grounding bodies laid underground should not be painted.

3. Requirements for grounding body size
The diameter of the round steel is 8mm; the thickness of the angle steel is 4.5mm; the wall thickness of the steel pipe is 3.5mm; the cross section of flat steel is 4*12mm2, and the thickness is 4mm. The grounding device must be effectively connected and should be laid in a place that is easy to check. The above is the minimum size marking of the grounding body. The size can be one size larger during actual construction.

4. Summary
The electrostatic grounding of gas stations is a systematic and highly professional work, which is directly related to the safe operation of gas stations. It is necessary to strictly follow national and industry specifications, select qualified materials, ensure construction quality (reliable connection, corrosion protection in place), and establish a complete inspection and maintenance system. There must be no carelessness, otherwise it will bury major safety hazards. If you encounter uncertain problems in specific construction, be sure to consult professional engineers or institutions. Safety is no small matter, and every link needs to be taken seriously.