CNG refueling station storage equipment includes storage cylinders, well pipes, and spherical tanks.
1. Storage Cylinders
CNG station storage cylinders refer to specialized storage cylinders conforming to the “Station Compressed Natural Gas Cylinders” standard GB19158, with a nominal pressure of 25MPa (gauge pressure), a nominal volume of 50~200L, and a design temperature ≤60°C. They are also simply referred to as cylinders. The medium used is natural gas conforming to the “Vehicle Compressed Natural Gas” standard GB18047. Some manufacturers also produce storage cylinders with a nominal volume of 40L. There are also storage cylinders made of composite materials with a nominal volume of 40~80L, but their current application performance is not ideal.
In engineering practice, cylinders with a nominal volume of 80L or less are commonly called small cylinders, and storage cylinders with a nominal volume of 500~1750L are called large cylinders. Large cylinders are manufactured according to standards such as GB150 “Steel Pressure Vessels”, GB 5099 “Seamless Steel Gas Cylinders”, and JB4732 “Steel Pressure Vessels – Analytical Design Standard”, or according to imported international standards approved by my country. In CNG stations, a group of several to dozens of gas cylinders connected to form a larger storage volume is called a cylinder group. Small cylinders are generally grouped in sets of 20-60, with each group having a nominal volume of 1.0-4.08 m3. Large cylinders are generally grouped in sets of 3, 6, or 9, with each group having a nominal volume of 1.5-16.0 m3. Each group is fixed with a steel frame, skid-mounted, and equipped with inlet and outlet pipes. Small cylinders are relatively cheaper, but have more seals, valves, and inlets, resulting in a relatively higher chance of leakage. Large cylinder groups have far fewer seals, valves, and inlets, resulting in a very low chance of leakage and easier maintenance, but they are much longer, reaching nearly 11.5 m. Cylinder-type gas storage equipment is suitable for all CNG stations, especially for substations and small-scale gas stations. The cylinder-type equipment is supplied as a complete set, with the assembly configuration shown in the diagram below. Each set includes inlet/outlet valves, safety valves, and drain valves, and can also be equipped with pressure gauges and thermometers as needed. It can be directly selected or assembled according to the designed gas storage pressure regime and corresponding capacity.

2. Well Pipe
CNG storage well pipe is short for vertical high-pressure gas storage pipe. The well pipe should comply with the requirements of SY/T6535 “High-Pressure Gas Underground Storage Wells,” with a nominal pressure of 25MPa (gauge pressure), a nominal volume of 1~10m3, and a storage medium of natural gas conforming to GB18047 “Compressed Natural Gas for Vehicles.” The well pipe consists of a bottom end cap, well casing, and wellhead assembly, as shown in the diagram above. The well casing should meet the requirements of API Spec 5CT. The casing steel grade should be TP80CQJ, with an actual yield strength of 552~758MPa and an actual tensile strength of 689~862MPa. The actual tensile strength of the wellhead equipment material should not exceed 880MPa, and the actual yield strength ratio should not exceed 0.9. SY/T 6535 specifies the outer diameter of the casing as 177.80~6273.10mm. The footprint of the well casing is related to the well inclination angle. In actual engineering, when the well casing length (depth) is less than 100m, and the well inclination is well controlled, each well only needs to occupy 1m2. Well casing is suitable for CNG stations without underground buildings (structures) and where safety distances are limited. It should not be built in areas prone to geological disasters, such as landslides or areas with underground cavities.

3. Spherical Tanks
With the same volume, spherical tanks consume less steel and occupy less space than gas cylinders, making them suitable as gas storage equipment for CNG stations. Spherical tanks used in CNG stations should comply with the requirements of GB150 “Steel Pressure Vessels”, with a nominal pressure of 25 MPa and a nominal volume of 2~10 m3. Due to limitations in manufacturing processes, the strength of the materials used in CNG station spherical tanks should not be too high. Therefore, their walls are relatively thick, the homogeneity of the shell plate material is relatively poor, and manufacturing is more difficult. Therefore, this needs to be considered during the design and selection process.