1. Gas station measuring instruments and their use
1.1 Dipstick
The oil level in the oil tank is measured using a dipstick with a nominal length of 5m. It consists of a weight, a ruler frame, and a ruler tape, and its minimum graduation value is 1mm. Two consecutive measurements are required. When the difference between the two readings is no more than 1mm, the first reading of the two readings is taken as the oil measurement result.

1.2 Water gauge
The water level in the oil tank should be measured regularly and drained in time.

1.3 Thermometer
To measure the oil temperature in the oil tank and the temperature of the sample, use a precise, fully immersed, rod-type mercury thermometer with a minimum graduation value of 0.2°C.

1.4 Standard container
The gas station is equipped with a 20L standard container for self-calibration of the gas station.

2. Basic knowledge of oil measurement
At present, the measurement of oil products at home and abroad is divided into two types: weight measurement and volume measurement. For gas stations, they measure by volume when selling, but they measure by weight when purchasing, which is usually called “tons in and liters out”, and they also measure by volume, which is usually called “liters in and liters out”. Both methods have their advantages and disadvantages.
2.1 Calculation of volume measurement
Due to the expansion and contraction of oil products, the volume of the same oil product is different at different temperatures. Therefore, in the measurement of oil products, any volume without indicating the temperature is meaningless. My country calls 20°C the standard temperature of oil products, so the volume of oil products at 20°C is the standard volume, expressed as V20. Gas stations generally sell according to the volume at the actual temperature t°C of the oil product, that is, Vt. If the oil is purchased at a lower temperature and sold at a higher temperature, it will be profitable, otherwise it will be a loss.
The volume change of oil products when the temperature changes from t1 to t2 can be expressed as follows:
V20=VCF*Vt
VCF: called volume correction factor, which can be obtained by checking GB/T-1885-1998 “Petroleum Measurement Table” or other related tables.

2.2 Calculation of weight measurement
For gas stations that enter and exit by tons, weight measurement must be issued during acceptance; for gas stations that enter and exit by liters, if the ground scale is used for handover, there is also the problem of conversion between volume and weight.
According to the basic formula for oil volume calculation recommended by GB/T1884-1998:
m =(ρ20-1.1)*VCF*Vt
ρ20: Density at 20°C, which can be obtained by measuring the apparent density ρt and the test temperature t in the oil sample, and then checking the “Standard Density Table of Petroleum Products”.
VCF: Volume correction factor, which can be obtained by checking the “Volume Correction Factor Table of Petroleum Products” through the oil temperature t and ρ20.

3. Oil loading and unloading operation steps
1) After the tanker arrives at the station, the driver should be instructed to stop at the specified position;
2) Do a good job of static grounding;
3) Check the outbound documents to confirm the name, specification, and quantity of the oil;
4) Check the lead seal, valve, vehicle condition, and leakage;
5) After parking for 15 minutes, get on the vehicle for measurement. First, put the thermometer with an insulation box into the middle of the liquid to measure the water height, then measure the oil height, measure the oil height twice, and finally take out the thermometer to read the temperature;
6) Check the volume table to calculate the volume of the oil at the measurement temperature;
7) Carry out acceptance according to the different requirements of volume measurement and weight measurement, and calculate the transportation loss.