Automatic Tank Gauging System (ATG)

Automatic Tank Gauging System (ATG) consists of a liquid level gauge controller, a magnetostrictive level gauge, a management server, management software, and other components. Through the tank level, the average temperature, and other data can be accurately measured, effectively managing gas station Invoicing And shift, and other business. The system can monitor 1-6 tanks simultaneously, fully realizing the closed measurement and data quasi-safety. Indeed, safety, at the same time, includes side leakage alarm, accident alarm, liquid level alarm, and other functions. Petrol stations can be full of monitoring, fully automated petrol station management, and intelligence.

Automatic Tank Gauging System (ATG)

 

ATG control box

The console is the interface of customer operation, and the display is also the data management and record center. The major units of the console are the power board, mainboard, touch screen, and safety barrier. Through the reduced voltage from the power board, it will supply a safety voltage and current status for the whole system.

RT Liquid Console

RT Liquid Console

 

Composition of the ATG control box

  1. TFT 8-inch color touchscreen, 800×600 resolution, graphical touchscreen control, intuitive and fast
  2. Core processing motherboard, Consists of high-end embedded processors and peripheral circuits, which are the data processing center of the entire liquid-level measurement system
  3. Safety barrier, The safety barrier is an explosion-proof safety isolation component, which outputs safe and reliable current and voltage to provide probe work
  4. Power module: The power module provides stable power to the entire control box

Main parameters of the ATG control box

  1. Working power: AC220V 0.2A 50/60HZ
  2. Operating temperature: -20℃~60℃
  3.  Can monitor the oil level, water level, density, volume, and temperature of 12 oil tanks at the same time
  4. Automatic alarm and manual alarm release
  5. Automatic generation of oil inlet report, inventory report, alarm report, and leakage report
  6. Automatic tank table generation and correction
  7. Leakage monitoring function
  8. Tank table data entry and export
  9. An open networking protocol that can be connected to other companies’ management systems

User interface

RT Liquid Console

 

 

ATG probe rod

The probe rod of the liquid level meter is also called the sensor. It is developed based on the principle of magnetostriction

ATG Probe Rod

Composition of the probe rod

It is mainly composed of magnetostrictive wire (waveguide wire), measuring rod, electronic chamber, and non-contact float (with a permanent magnet inside) on the rod

The structure is shown in Figure P1. When the sensor is working, the electronic chamber sends a “starting pulse”, which is transmitted along the waveguide wire and generates a rotating magnetic field. When the magnetic field meets the permanent magnetic field of the float, a magnetostrictive effect is generated, causing the waveguide wire to twist. The electronic chamber senses the twist and converts it into an “end pulse”. By calculating the time difference between the two pulses, the displacement is measured, thereby obtaining an accurate liquid level value.

Probe Rod

Main parameters of the probe

  1. Power supply: +24VDC (+10%)
  2. Operating temperature: -40~+85℃
  3. Operating current: <40mA
  4. Measurement object: 1~3 positions, 1~5 temperature points
  5. Temperature measurement range: -40~+85℃
  6. Transmission mode: RTU
  7. Communication interface: Standard EIA-RS485/RS422
  8. Protection level: IP65

More details

Automatic Tank Gauging System

Bluesky Automatic Tank Gauging System

How to know the liquid level inside the oil tank?

Liquid Level Gauge Tank Capacity Table Functional Design

Analysis of False Losses in Gas Station Fuel