Safety Details Often Overlooked During Oil Tank Cleaning

In July 2023, a flash explosion occurred at an oil depot in Guangdong while a 5,000-cubic-meter gasoline tank was being cleaned, resulting in serious injuries to two people. A subsequent investigation revealed that, although combustible gas concentrations had been measured and a work permit issued before the operation, the procedure was flawed: gas sampling was conducted only at the manhole, completely missing “dead zones” at the bottom of the tank.

This is not an isolated case. Tank cleaning is one of the highest-risk routine operations in the refined oil sales sector; however, accident records show that failures often stem not from a lack of protective measures, but from measures that were executed incorrectly or incompletely. Almost every safety officer can recite these requirements by heart.

Oil tank cleaning operations

Gas Detection: Are You Testing the Right Locations?

Let’s look at the data first. The standard GB 30871-2022 mandates that gas analysis be performed within 30 minutes before confined space operations.

Insert a multi-gas detector (typically a “four-in-one” unit) through the manhole, wait 30 seconds, verify that the readings are within limits, and sign off to begin work.

Areas such as the tank bottom, beneath baffles, around internal floating roof seals, and in recesses near outlet nozzles are “blind spots” where vapors accumulate. In a 2021 accident, the detector showed normal readings at the manhole, yet when a worker descended to the bottom and bent over to work, the vapor concentration at knee level reached 40% of the LEL—a depth the detector had never reached.

Using an extension sampling probe, the detector should remain at each location for a duration exceeding its response time—typically 15 to 30 seconds.

Protective Equipment

Everyone is familiar with the standard equipment list for tank entry operations: gas masks, protective suits, safety lines, and explosion-proof two-way radios. It looks comprehensive enough.

However, two points are seriously underestimated. The first concerns the filter canisters for gas masks. Gasoline vapors contain benzene compounds and n-hexane; while standard organic vapor filter canisters (Type A) can indeed filter these out, the adsorption capacity begins to degrade the moment the canister is unsealed, even if it isn’t being used. Some sites use a single box of canisters for six months—long after they have lost their effectiveness.

The second point is even more critical: static electricity. When high-pressure water jets are used to wash tank walls, the rate of static generation through friction far exceeds the rate at which a grounding wire can dissipate the charge. In a 2019 accident at an oil depot, a cleaner wearing a synthetic-blend work suit accumulated static electricity while spraying the tank wall; the charge discharged onto the metal tank body, igniting residual oil vapors.

Anti-static measures involve more than just attaching a grounding wire. Before entering the tank, personnel must discharge static electricity using a grounding ball for at least five seconds. The nozzle of the high-pressure water gun also requires its own separate grounding—a requirement often completely omitted from operating manuals.

Oil Tank Cleaning

Handling of Residues

Tank cleaning generates large quantities of oily wastewater and tank-bottom sludge. There are two major pitfalls here. The first is the spontaneous combustion of sludge. Sludge from crude oil and heavy refined oil tanks contains ferrous sulfide, a substance that oxidizes.
If the sludge accumulates to a certain thickness and heat cannot dissipate quickly enough, the temperature can spike above 300°C, directly igniting surrounding combustible materials. In 2018, in a location in Shandong, sludge removed during cleaning was piled outside the tank farm’s containment bund; it spontaneously ignited in the early hours of the next day, burning three nearby tanker trucks. The second issue concerns environmental risks associated with wastewater disposal. A more insidious problem arises when sites temporarily store wastewater in open-air pits, intending to have it hauled away “in a few days,” only to have a heavy rainstorm cause the pit to overflow, washing residual oil into nearby farmland. Once environmental authorities conduct tests, the resulting fines start in the six-figure range.

The disposal procedure is straightforward: once removed, oily sludge should be placed in lidded metal drums, kept away from heat sources and tank farms, and collected by a licensed hazardous waste disposal contractor on the same day. Oily wastewater should be processed in an oil-water separator; the floating oil layer is recovered, while the underlying water is discharged only after testing confirms it meets compliance standards.