As one of the core pieces of equipment of gas stations, the normal operation of fuel dispensers directly affects business results; refined oil is a flammable and explosive hazardous chemical, which is prone to accidents due to uncontrollable factors such as operational risks and traffic accidents during business activities. Standard gas stations will install special cut-off valves for such fuel dispensers to ensure that the losses and hazards to customers and gas stations can be minimized when sudden safety incidents occur.

Why install a cut-off valve?
However, some gas station operators believe that installing a cut-off valve is unnecessary, and some only install a simple ball valve as a cut-off valve. Such practices will pose dangerous hidden dangers. So today, I will share with you why submersible pump fuel dispensers need to be equipped with cut-off valves.
First of all, we have to start from the overall pipeline control system and the actual oil distribution of submersible pump gas stations:
A submersible pump may supply oil to multiple fuel dispensers and multiple oil guns at the same time. From the actual operation principle, whether the submersible pump works or not is controlled by the oil gun switch of the supplied machine; that is, any oil gun switch corresponding to the submersible pump can control the submersible pump to start the oil supply function when it is turned on.
However, in reality, if the fuel dispenser is knocked over by external force, ensuring that the oil in the corresponding pipeline does not overflow and spray after the fuel dispenser is knocked over is particularly important.
According to the national standard GB50156-2012 “Code for Design and Construction of Gas Stations”.
That is, installing a shear valve ensures that the fuel dispenser will automatically close the valve when subjected to external impact, high temperature, fire, etc., to ensure that the oil does not leak and play a safety protection role.
Cut-off Valve Parameters:
- Oil pressure test: The cut-off valve does not leak under the 1.4MPa oil pressure test.
- Cut-off test: It breaks under the bending moment of 350N•m~880N•m, and there is no leakage at the valve port after breaking, which meets the cut-off requirements.
- Fusing test: When the rotating arm is at 76°C, the emergency cut-off valve closes automatically, and there is no leakage at the valve port after closing, which meets the fire protection requirements.
- According to the medium used: divided into a liquid cut-off valve and an oil and gas recovery cut-off valve.
Cut-off Valve Classification:
- Classified by structure: Type 1 cut-off valve (main valve, temperature switch, check valve, and pressure relief valve), Type 2 cut-off valve (main valve and temperature switch), and Type 3 cut-off valve (main valve).
- Note: Type 1 and Type 2 cut-off valves are used in liquid pressure systems, and Type 3 cut-off valves are only used in oil and gas systems.
- At present, the two ends of the commonly used liquid emergency cut-off valve for fuel dispensers are 1.5-inch internal threads.

Key Points for Using Cut-off Valves:
- The pipe thread seal at both ends of the valve’s oil inlet and outlet must be sealed with oil-resistant pipe thread sealant. The use of polytetrafluoroethylene tape (raw material tape) is strictly prohibited.
- The on-site foundation must be constructed in accordance with the corresponding equipment foundation construction drawings to ensure a reliable fixed position for the cut-off valve.
- The anchoring device (fixing the shear valve) must be able to withstand a force greater than 650 foot-pounds (900N·m) on each valve.
- When you need to open the valve, turn the rotating arm counterclockwise, lift the connecting rod, let the pin on the rotating arm slide into the groove of the connecting rod, and the rotating arm will be fixed, keeping the valve in the normally open state. When you need to close the valve, you can turn the rotating arm counterclockwise a little to push the connecting rod away, and the rotating arm will automatically spring back clockwise and close the valve.
- During the maintenance of the fuel dispenser’s hydraulic system or the cleaning (replacement) of the fuel dispenser’s filter screen, the oil circuit of the fuel dispenser’s inlet pipe can be cut off by closing this valve to prevent the danger of oil injection during the maintenance of the fuel dispenser.