To address the long-standing challenges facing service stations—such as leakage risks, inefficient refueling, and complex operations and maintenance—Bluesky leverages its extensive experience in the research, development, and application of fuel storage equipment to provide a comprehensive solution. This solution covers every aspect of the system: from the fundamental properties of SF (steel and FRP) materials and the integration of submersible pumps to the standardized installation of access sumps. In this way, service stations of any size can implement safe, efficient, and compliant fuel storage systems, effectively resolving recurring operational issues such as leaks, spills, and supply interruptions.

Overview of key features of SF-material oil tanks
Bluesky’s full range of fuel storage equipment utilizes the industry-standard SF-type double-walled structure, establishing a robust dual-layer defense for safety and environmental protection:
- Inner tank: Manufactured using high-quality Q235B carbon steel and automated welding processes. Each unit undergoes rigorous non-destructive, hydrostatic, and leak-tightness testing, ensuring structural strength far superior to conventional single-walled steel tanks, as well as the ability to withstand long-term soil pressure and static fuel pressure in underground environments.
- Outer protective layer: A fiberglass-reinforced plastic (FRP) layer exceeding 4.0 mm in thickness encases the inner steel tank, creating a continuous, corrosion-resistant barrier. This layer completely isolates the tank from electrochemical corrosion caused by groundwater or saline-alkaline soils, extending its service life to over 30 years—significantly surpassing that of traditional single-walled tanks.
- Double-walled design with interstitial space: A continuous interstitial space (ranging from 0.1 to 5 mm) is maintained between the inner and outer tanks, equipped with a 24-hour active leak monitoring system. In the event of a minor leak in the inner tank, fuel flows directly into the interstitial space rather than seeping into the soil or contaminating groundwater; simultaneously, the system triggers audible and visual alarms and sends remote alerts, enabling operations and maintenance personnel to immediately address potential risks.
- Diverse specifications: The product series offers capacities ranging from 10 m3 to 50 m3, covering a wide range of applications—from small rural service stations to high-capacity storage requirements for large oil depots and industrial facilities. All products are CE explosion-proof certified and fully comply with local safety and regulatory standards in regions such as Latin America and the Middle East.

Submersible Pump Compatibility and Installation Tips
The Bluesky SF submersible pump is designed to adapt to a wide range of operating conditions. A standardized process—covering everything from model selection to installation—effectively prevents common failures caused by incompatibilities between the equipment and its operating environment:
- Selection Guide: Standard explosion-proof submersible pumps are suitable for dispensing conventional diesel or standard gasoline. If a service station needs to dispense slightly corrosive fuels (such as E10 ethanol-blended gasoline), an alcohol-resistant model should be selected; this prevents seals and impellers from deteriorating or swelling due to prolonged contact with corrosive agents, which could otherwise lead to fuel leaks or air ingress in the piping. For station renovation projects, it is recommended to prioritize pumps equipped with an integrated, high-precision pre-filter. This component traps sludge and impurities accumulated in the fuel tank, thereby minimizing the risk of impeller or pump body blockages at the source.
- Pre-installation Inspection: Upon receiving the equipment, inspect the pump body for deformation or cracks and manually rotate the impeller to ensure it moves smoothly without binding. Use a multimeter to check the motor’s insulation resistance; the reading must exceed 200 MΩ before installation to prevent electrical leakage during operation.
- On-site Installation Standards: The pump must be installed vertically on the internal support pipe, with a tilt angle of no more than 15°, to prevent uneven impeller wear during prolonged operation. Inlet and outlet piping must be secured with dedicated supports to prevent displacement caused by vehicle traffic or ground settlement—factors that could place stress on or obstruct the pump body. Once the wiring is complete, perform a 30-minute no-load test run; the pump may only be put into official service after confirming that the motor is operating correctly and the pressure gauge reading is stable.

Standardized Adaptation and Construction of Manholes
- Key product advantages: Manufactured from SMC composite material using a single-stage molding process, the product offers excellent dimensional consistency, resistance to deformation, and high interchangeability. Its overall structural strength far exceeds that of traditional metal manways. Pre-set alignment reference lines allow for rapid, precise alignment with the manway flange of steel and FRP (SF) storage tanks during installation, and the product is compatible with various tank diameters.
- Installation steps: First, sand the outer FRP layer within a 150 mm radius around the tank manway to roughen the surface and remove all dust. Next, position the composite waterproof flange, aligning it with the tank’s axial reference line, and seal the joint using a specialized sealant. Once the sealant has initially set, apply a bonding and reinforcement layer using resin and fiberglass mesh compatible with the material of the tank’s outer layer. Finally, install the manway once the entire assembly has fully cured.
Smart Management System Features
Bluesky’s patented smart fuel storage management system utilizes RFID technology to integrate seamlessly with steel-fiberglass (SF) double-walled tanks, submersible pumps, and manholes, enabling fully digital, end-to-end control of the entire storage process:
- During tanker unloading, the system automatically records the total fuel volume and reconciles it with dispenser sales data, thereby eliminating the “unexplained losses” of hundreds of liters of fuel that often occur due to manual data recording.
- Equipped with an IoT data transmission unit, the system synchronizes real-time information—such as liquid levels, temperature, and inventory—with mobile devices via Cat.1 networks, even in remote areas with poor connectivity; this eliminates the need to manually climb tanks or perform on-site physical inventory checks.
- All dispensing operations require RFID card authorization; unauthorized personnel cannot extract fuel from the tank, effectively preventing fuel theft and data tampering.
Routine Maintenance Recommendations
Following these operational guidelines can extend the service life of the entire fuel storage system by over 30% and significantly reduce long-term operating costs:
- Perform a pressure test on the tank’s interstitial space (the gap between the inner and outer walls) every quarter; monitoring pressure fluctuations allows for the rapid detection of potential leaks in either tank wall.
- Clean debris from the submersible pump’s impeller chamber and lubricate the bearings with high-temperature lithium-based grease once a month; this prevents sediment buildup from clogging the impeller, thereby extending the pump’s service life.