The safety risk of gas station oil tank clearance has always been the highest level of gas station risk.
On the one hand, tank cleaning is a common content in gas station construction projects.
On the other hand, it involves special operations such as temporary electricity consumption and confined space, which is highly professional.
The on-site employees of the gas station often have an insufficient understanding of on-site risks and do not supervise and manage them in place.
The preventive measures of the clearance unit are not matched, and the staff does not carry out construction operations according to the operating procedures, which is very prone to accidents.

1. Let’s turn to 2 main issues
A) The contradiction between tank clearance and hazardous waste disposal
Clearance produces a lot of hazardous waste. Taking the 120m3 underground oil tank as an example, manual tank clearing often produces 100~200L of hazardous waste. The mechanical clearance produces a danger of 1000 ~ 2000L
hazardous waste. These include oily effluent during tank clearance as well as sludge impurities with water.
The hazardous waste treatment process involves the temporary storage and disposal of hazardous waste.
Every country now has strict regulatory requirements for this.
For the hazardous waste collected in the process of clearing, the gas station shall not dispose of it at will or directly take it away by the clearing unit or sell it without authorization and must be handed over to a regular hazardous waste disposal unit for disposal.
Moreover, because most government departments have strict management of temporary storage of hazardous waste, gas stations often need to avoid long-term storage of hazardous waste as much as possible and need to contact the hazardous waste disposal unit in advance to dispose of hazardous waste as soon as possible after the implementation of clearance.
B) The contradiction between clearance safety and oil and gas emission supervision
During the clearance process, the manhole well must be opened so that the submersible pump and level gauge can be disassembled, and cleaning equipment or personnel can be entered.
To ensure safety, it is also necessary to stop using the vapor recovery unit.
To ensure the safety of the tank clearance process, both mechanical cleaning and manual cleaning require the oil tank to be blown before tank clearance.

Manual cleaning must be carried out in advance to reduce the concentration of oil and gas and ensure that the concentration of oil and gas is within the specified range before confined space operations can be carried out.
Some government departments require the recovery of oil and gas from the blast, but there is no corresponding mature and economical technology.
Once the oil and gas concentration is found to be exceeded, the government may directly punish the gas station.
2. Attention measures
A) Clarify the responsibilities of the tank cleaning management department, and comprehensively coordinate the tank clearance needs of gas stations.
It is recommended that the Department of Gas Station Equipment Management be responsible for establishing a gas station clearance account.
In addition to emergency response, the transformation, deformation, miscellaneous cleaning, volume calibration, and other regular inspections of the tank should be combined.
There is also a need to reduce frequent clearances to reduce the volume and risk of operations.
B) Scientifically formulate the clearance cycle.
Except for special circumstances such as emergency, transformation, and variability, the tank should be set up in combination with the needs of miscellaneous cleaning, inspection and maintenance, and regular inspection.
With the upgrading of oil standards, the process of hydro-refined oil deterioration during storage to form gum and asphaltene has become slower.
Most companies set the clearance cycle at 3~5 years.
But in fact, the amount of oil residue in the tank after 5 years of use is not much, especially the gasoline tank.
However, some flowable impurities are brought out of the tank through the filter screen of the dispenser or the dewatering filter element and do not deposit too much at the bottom of the tank.
Therefore, the clearance cycle of the oil tank should be mainly determined by the regular maintenance or inspection time of the oil tank.

C) The selection of clearance method should not only consider safety and environmental protection but also consider the quality of clearance, as well as the cost (including clearance time, expenses, etc.).
When the mechanical tank cleaning is selected, the water jet design of the cleaning equipment should be done, and the flushing water volume can meet the cleaning requirements within 30~150L/m2.
Cleaning underground tanks at a gas station is not a simple task.
Whether it is the preliminary preparation or the later operation process, we need to do each step carefully and carefully.